Hybrid Rack Transfer Switch with
Outlet-Level Metering and Switching
Raritan’s hybrid rack transfer switches use electromechanical relays and silicon-con-
trolled rectifiers (SCRs) to transfer a load between two sources. The result is perfor-
mance and reliability that exceeds that of standard automatic transfer switches (ATS)
and at a lower price point than static transfer switches (STS).
Industry Leading Performance
• Uses SCRs to provide STS-like transfer times and eliminate electrical arcing and welding
of relays; hybrid relay plus SCR-design allows hand off of the transferred load to a relay,
making it power efficient and producing less heat.
• Current sampling at 4,800 times per second for load transfers within 4 to 8ms.
• The PX3TS-5000 series features outlet-level metering and switching.
• Only rack transfer switch with power metering, energy quality monitoring and support
for optional environmental sensors.
• Local and remote web-based monitoring, and control, and alarms.
Designed with Maximum Reliability in Mind
• Oversized relays, rated at 48A, and SCRs, rated at 70A, even though the transfer
switches are intended for 16A and 32A loads.
• Prevents transfers of output short circuits which could lead to failure of the second
power feed.
• Uses two single throw relays instead of one double throw relay (a single point of failure)
to support reliable out-of-phase transfers.
• Hybrid design eliminates out-of-phase transfer problems like arcing and provides more
deployment options since the feeds do not have to be the same phase.
• Uses relays with an air gap of 3.3mm vs. the 0.6mm gap used in most transfer switch
relays on the market. Prevents arcing due to surges.
• Offers a 30% larger relay contact surface area to handle larger currents.
• Offers surge protection, field replaceable output short protection, redundant internal
power supplies and controllers.
Intelligent Rack Transfer Switch
Features
• Load transfer times 4–8ms.
• Reliable transfer between sources
regardless of phase.
• Over-sized relays (rated 48A) and
SCRs (rated 70A).
• Eliminates electrical arcing that leads
to transfer relay failure.
• 3.3mm vs. typical 0.6mm contact air
gap to prevent arcing due to surges.
• Inlet surge protection and field
replaceable, fast-blow fuses for short
circuit protection.
• Inlet or outlet-level metering and
switching, with power quality
monitoring.
• User configurable thresholds for
power quality.
• Ethernet, Modbus, and SNMP
networking.
• USB ports for Wi-Fi, camera, tablet,
and cascading.
• Alarm and status updates via GSM
text, email and syslog.
• Supports Raritan plug-and-play
environment sensors.
• Runs in up to 60º C (UL), 50º C (CE)
environment at 85% RH.
• Energy efficient and
produces less heat.
• 20W power consumption.
• SecureLock
™
ready to prevent
accidental disconnects.