APPENDIX H: FAQ 101
SUBJECT:
QUESTION:
ANSWER:
I have a P2ZCIM beeping every
30-40 seconds. Also I noticed
that the LED is blinking very
rapidly. Why is this
happening?
A P2ZCIM will beep once every
minute to notify the user that it
did not get a Communication
Address. The user should check
to make sure that the number of
CIMs has not exceeded the Chain
size. If the size is correct, the
problem should disappear after a
couple of minutes. If not, check
again to make sure the chain size
is correct. The beeping CIM will
increase the Communication
Address Request delay to 40-55
seconds. The data collision
introduced by continued
Communication Address requests
should not affect keyboard and
mouse functionality, however if
there are many units which can
not get Communication
Addresses it might cause slower
keyboard and mouse
response. Beeping CIMs can also
occur if the 2 chains are
connected together to make one
chain.
The P2ZCIM beeps when it
first receives power. Why?
This is normal operation. The
beep notifies the user that the
CIM has powered up correctly.
I connected a powered-on CIM
to another chain and now the
chain size is wrong. What
happened?
The CIM you added was a Master
CIM. When it was added to the
new chain, it became the Master
of that chain as well. The added
CIM reset the chain to use its’
last known chain size. The user
should momentarily power off a
CIM before adding it to a new
chain to prevent this problem.
The user can resize the chain to
correct this issue.
What would happen if I
attached 4 DZCIMs and 4
P2ZCIMs in the same chain?
A DZIM master won't add a
P2ZCIM Slave. A P2ZCIM
Master won't add a DZIM
slave. It detects this by looking at
the serial number of the unit
requesting a communication
address. The chain will either be
a P2ZCIM or DZCIM chain. It
depends on which CIM becomes
the master first. Users should
never connect P2ZCIMs to
Dominion KX, and they should
never connect DZCIMs to
Paragon. The DZCIM will be
unable to create a database on a
Paragon unit. The P2ZCIM will
be unable to create a database on
a KX unit.